Epoch Form:
Inspection: Creative Surveying, Pinnacl X, Mesa
Line #’s: For multi-curcuit structures, oder lines from highest to lowest voltage. If two lines have same voltage, lowest line # comes first.
Structure #’s: For multi-curcuit structures, oder lines from highest to lowest voltage. If two lines have same voltage, lowest line # comes first.
Region: CT, NH, EMA (Eastern Mass), WMA (Western Mass)
Designation: SCSP, SCWP, SCLP, DCWP, DCSP, DCLP, SCHF-WP, SCHF-LP, DCLT, Terminal, Other
Structure Construction Material: Galvanized, Weathering, Natural Wood, Laminate Wood, Concrete, Fiberglass, Painted Steel
Line/Bent (Steel): A-No Action, B-Minimal, C-Moderate, D-Severe
Shell Rot: A-No Action, B-Minimal, C-Moderate, D-Severe, N/A
Rust (Steel): A-No Action, B-Minimal, C-Moderate, D-Severe, N/A
Decay (Wood): A-No Action, B-Minimal, C-Moderate, D-Severe, N/A
Pole Splits/ Breaks: A-No Action, B-Minimal, C-Moderate, D-Severe, N/A
Fracture: A-No Action, B-Minimal, C-Moderate, D-Severe, N/A
Insect Damage: Yes, No, N/A
Woodpecker Holes (Location): N/A, Top, Middle, Bottom, Longitudinal to conductor, Transverse to Conductor
Woodpecker Holes (Severity): A-No Action, B-Minimal, C-Moderate, D-Severe, N/A
Danger signs missing/damaged: Yes, No, TBD
Guy Anchor Marker: Yes, No, N/A, TBD
Guy/Anchor Problems: None, Loose, Disconnected, Rusty
Hardware Damage: A-No Action, B-Minimal, C-Moderate, D-Severe
Crossarm Damage (Severity): A-No Action, B-Minimal, C-Moderate, D-Severe, N/A
Crossarm Splits/Breaks: A-No Action, B-Minimal, C-Moderate, D-Severe, N/A
Down Lead/GW Problems: Disconnected, Loose, Missing, No Issue, TBD
Insulator Configuration: Strain, Suspension, Both, Other
Insulator Condition: A-No Action, B-Minimal, C-Moderate, D-Severe, N/A
Num. Insulator Chipped/ Broken per Strings: 0,1,2,3,4,5,6,7,8,9,10+
Conductor Damage (Severity): A-No Action, B-Minimal, C-Moderate, D-Severe
Conductor (Location): N/A, Bottom, Middle, Top, East, West, South, North
Conductor Strands: A-No Action, B-Minimal, C-Moderate, D-Severe
Conductor Splice: A-No Action, B-Minimal, C-Moderate, D-Severe, N/A
Conductor Attachment Point: A-No Action, B-Minimal, C-Moderate, D-Severe
Conductor Burned: A-No Action, B-Minimal, C-Moderate, D-Severe, N/A
PCS Antennas on Structure: Yes, No
FAA Lighting: Yes, No, Not Functioning
Marker Balls: Yes, No, (If damaged, add comment below)
Lighting Arrestor (LA): Yes - chain intact, Yes - chain disconnected, N/A
OPGW Splice Can & Grounding Installed Correctly: Yes, No, N/A
Culvert Open: Yes, No, N/A
Culvert Condition: A-No Action, B-Minimal, C-Moderate, D-Severe, N/A
Line Angle: Tangent, Angle
Ground Clearance Concern: Yes, No
High Brush/Trees: Yes, No
Hazardous Trees: Yes, No
Access Problems: Accessible by vehicle, Accessible by utility vehicle, Accessible only by foot, Not Accessible, Not accessible due to unexpected condition
Steps Lower than 12 Feet: Yes, No
Encroachments: Yes, No
Erosion: A-No Action, B-Minimal, C-Moderate, D-Severe
Bird Nest: Yes, No
Counterpoise: Yes, No
Overall Structure Condition: A-No Action, B-Minimal, C-Moderate, D-Severe
Misc. Problems: A-No Action, B-Minimal, C-Moderate, D-Severe, None
Assigned To: PinnaclX
Reason for Not Being Inspected:
AGL (Feet):
Misc. Notes:
Inspection Date:
Lead Inspector Name: Al Gates
Vendor Reviewer QA/QC: K. Swift Date:__________
ES Reviewer: Name:___________ Date:__________